Comm Series PS 220 40A to 100A
PolyPhaser Home Page ICT Home Page

 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
Model
ICT24012-40A
ICT24012-60A
ICT24012-80A
ICT24012-100A
Input Voltage Range (Vac)
90 to 270
90 to 270
90 to 270
90 to 270
Output Voltage (Vdc)
13.8 +/- 150mV
13.8 +/- 150mV
13.8 +/- 150mV
13.8 +/- 150mV
Output Current (Amps)
 
 
 
 
    Continuous
40.0
60.0
80.0
100.0
    Peak
40.0
60.0
80.0
100.0
    Current Limit
42.0
63.0
84.0
105.0
Line Regulation (%)
0.10 (90 - 270 Vac)
0.10 (90 - 270 Vac)
0.10 (90 - 270 Vac)
0.10 (90 - 270 Vac)
Load Regulation (%)
0.5 (1 - 40 Amps)
0.5 (1 - 60 Amps)
0.5 (1 - 80 Amps)
0.5 (1 - 100 Amps)
Output Ripple (mV RMS)
30
35
35
35
Efficiency (% Minimum)
80
80
80
80
Operating Temperature (F)
-50 to 125
-50 to 125
-50 to 125
-50 to 125
Size Inches (L x W x H)
13.5 x 8.7 x 3.5
13.5 x 8.7 x 3.5
13.5 x 8.7 x 3.5
13.5 x 8.7 x 3.5
Weight (pounds)
11.2
11.8
12.2
12.2
List Price *
$299.95
$398.95
$466.95
 

Also available:
    Voltage / Current LCD Meter, add suffix M
    Rack mount, add suffix R

* The US list price is provided for relative comparison purposes, please call for pricing and availability.

 